type,circuit,level,name,comment,qq,zz,pbsb,id,*name,part,type,divisor/values,unit,comment
*r,
*w,
r,,,StatPowerOn,StatPowerOn,,,b509,0dcc00,value,,UIN,,,
r,,,StatOperatingHours,StatOperatingHours,,,b509,0dcd00,value,,UIN,,,
r,,,StatMonthOfInstallation,StatMonthOfInstallation,,,b509,0dce00,value,,UCH,,,
r,,,StatYearOfInstallation,StatYearOfInstallation,,,b509,0dcf00,value,,UCH,,,
r,,,Stat15MinBusTimeout,Stat15MinBusTimeout,,,b509,0dd000,value,,UCH,,,
r,,,StatRTOSErrorcode,StatRTOSErrorcode,,,b509,0dd100,value,,UIN,,,
r,,,StatRestarts,StatRestarts,,,b509,0dd200,value,,UIN,,,
r,,,StatRTOSErrorCounter,StatRTOSErrorCounter,,,b509,0dd300,value,,UIN,,,
r,,,Storage1Sensor2,Storage1Sensor2: Temperature of SP1 sensor,,,b509,0d0000,temp,,D2C,,°C,temperature,sensor,,UCH,0=ok;85=circuit;170=cutoff,,sensor status
r,,,CirPump2,CirculationPump2: State of the circulation pump,,,b509,0d0c00,value,,UCH,0=off;1=on,,
r,,,ThreeWayValveLoadingPump12,ThreeWayValveLoadingPump12: State of LP/UV1,,,b509,0d1000,value,,UCH,0=off;1=on,,
r,,,LegioPump2,LegioPump2: State of the legionella pump,,,b509,0d1100,value,,UCH,0=off;1=on,,
r,,,TeleSwitch,State of the Teleswitch,,,b509,0d0a00,value,,UCH,0=off;1=on,,
r,,,OneTimeCirSwitch,OneTimeCirculationSwitch: non-recurring circulation pump running period,,,b509,0d0b00,value,,UCH,0=off;1=on,,
r,,,IsInParty,IsInParty: Every bit of this byte represents a heating circuit; if bit is set the party function is activated for the corresponding HC,,,b509,0d4e00,value,,UCH,,,
r,,,HwcLaggingTime2,DhwLaggingTime2: Time pump is running after energy demand is met,,,b509,0d6100,value,,UCH,,min,minutes
w,,,HwcLaggingTime2,DhwLaggingTime2: Time pump is running after energy demand is met,,,b509,0e6100,value,,UCH,,min,minutes
r,,,FlowTempDesired2,DesiredFlowTemperature2: Flow setpoint if tank has an energy demand,,,b509,0d4600,value,,D1C,,°C,temperature
r,,,HcParallelStorageFillingEnabled2,HcParallelTankFillingEnabled2: Heating cuircuits can be loaded in parallel to an active tank loading,,,b509,0d5500,value,,UCH,0=no;1=yes,,
w,,,HcParallelStorageFillingEnabled2,HcParallelTankFillingEnabled2: Heating cuircuits can be loaded in parallel to an active tank loading,,,b509,0e5500,value,,UCH,0=no;1=yes,,
r,,,HwcLoadingDelay2,DhwLoadingDelay2: Time waiting for a heating demand in caser of solar gain,,,b509,0d6200,value,,UCH,,min,minutes
w,,,HwcLoadingDelay2,DhwLoadingDelay2: Time waiting for a heating demand in caser of solar gain,,,b509,0e6200,value,,UCH,,min,minutes
r,,,SpreadingHwcLoading,SpreadingDhwLoading: Offset for DHW flow temperature,,,b509,0d8800,value,,UCH,,K,
w,,service,SpreadingHwcLoading,SpreadingDhwLoading: Offset for DHW flow temperature,,,b509,0e8800,value,,UCH,,K,
r,,,LegioStartTime2,LegioStartTime2: Hour for legio protection,,,b509,0d8a00,value,,UCH,,,
w,,,LegioStartTime2,LegioStartTime2: Hour for legio protection,,,b509,0e8a00,value,,UCH,,,
r,,,NativeHwcCircuitDisabled,NativeDhwCircuitDisabled: Disable DHW,,,b509,0da900,value,,UCH,0=no;1=yes,,
w,,install,NativeHwcCircuitDisabled,NativeDhwCircuitDisabled: Disable DHW,,,b509,0ea900,value,,UCH,0=no;1=yes,,
r,,,NormalHwcHysteresis,NormalDhwHysteresis: The hysteresis for DHW loading,,,b509,0daf00,value,,UCH,,K,
w,,,NormalHwcHysteresis,NormalDhwHysteresis: The hysteresis for DHW loading,,,b509,0eaf00,value,,UCH,,K,
r,,,OperatingMode2,OperatingMode2: Operating mode of the water circuit,,,b509,0d2b00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
w,,,OperatingMode2,OperatingMode2: Operating mode of the water circuit,,,b509,0e2b00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
r,,,TempDesired2,DesiredTemperature2: Temperature setpoint of water tank,,,b509,0d3200,value,,D1C,,°C,temperature
w,,,TempDesired2,DesiredTemperature2: Temperature setpoint of water tank,,,b509,0e3200,value,,D1C,,°C,temperature
r,,,TeleswitchOperatingMode2,TeleswitchOperatingMode2: If the tele switch port is activated the water circuit operates in this mode,,,b509,0d3f00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
w,,,TeleswitchOperatingMode2,TeleswitchOperatingMode2: If the tele switch port is activated the water circuit operates in this mode,,,b509,0e3f00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
r,,,DateTime,date/time,,,b504,00,dcfstate,,UCH,0=nosignal;1=ok;2=sync;3=valid,,DCF receiver state,btime,,BTI,,,time,bdate,,BDA,,,date,temp,,D2B,,°C,temperature
r,,,Mode,Operation mode,,,b504,01,temp,,UCH,,°C,temperature,hwcmode,,UCH,0=disabled;1=on;2=off;3=auto,,hot water mode,ign,,IGN:2,,,,hwcmode_1,,UCH,0=disabled;1=on;2=off;3=auto,,hot water mode,mctype,,BI0:7,0=inactive;1=mixer;2=fixed;3=hwc;4=returnincr;5=pool;6=circulation,,mixer type,hex,,HEX,,,,daynight,,UCH,0=night;1=day;7=floorpaving,,day/night mode
w,,,SetTempDesired,Set desired temperature,,,b505,01,value,,UCH,,°C,temperature
w,,,SetMode,Set operation mode,,,b505,02,value,,UCH,0=disabled;1=on;2=off;3=auto,,hot water mode
w,,,SetFlowTempMin,Set min flow temperature,,,b505,0e,value,,UCH,,°C,temperature
w,,,SetFlowTempMax,Set max flow temperature,,,b505,0f,value,,UCH,,°C,temperature
r,,,Params,Parameters,,,b504,09,temp,,UCH,,°C,temperature,ign,,IGN:3,,,,mctype,,BI0:7,0=inactive;1=mixer;2=fixed;3=hwc;4=returnincr;5=pool;6=circulation,,mixer type,temps,,SCH,,°C,temperature,ign_1,,IGN,,,,temps_1,,SCH,,°C,temperature,temps_2,,SCH,,°C,temperature,ign_2,,IGN,,,
r,,,Status0a,Status flow temperature/mixer/pump/desired flow temperature,,,b504,0a,flowtemp,,D2C,,°C,temperature,mixer,,UCH,0=off;1=open;2=close,,mixer State,pump,,UCH,0=off;1=on,,,onoff,,UCH,0=off;1=on,,,flowtempdesired,,UCH,,°C,temperature
r,,,Status,Desired flow/status/flow/desired temperature,,,b504,0d,temp,,UCH,,°C,temperature,onoff,,UCH,0=off;1=on,,,temp_1,,D2C,,°C,temperature,temp_2,,UCH,,°C,temperature
r,,,Status16,outside temperature,,,b504,16,value,,D2C,,°C,temperature
r,,,Timer_Monday,Periods Monday,,,b504,02,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Monday,Periods Monday,,,b505,0901,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Tuesday,Periods Tuesday,,,b504,03,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Tuesday,Periods Tuesday,,,b505,0902,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Wednesday,Periods Wednesday,,,b504,04,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Wednesday,Periods Wednesday,,,b505,0903,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Thursday,Periods Thursday,,,b504,05,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Thursday,Periods Thursday,,,b505,0904,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Friday,Periods Friday,,,b504,06,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Friday,Periods Friday,,,b505,0905,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Saturday,Periods Saturday,,,b504,07,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Saturday,Periods Saturday,,,b505,0906,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Sunday,Periods Sunday,,,b504,08,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Sunday,Periods Sunday,,,b505,0907,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,install,Iotest,I/O test,,,b506,02,value,,UCH,0=valve1;1=cirpump;2=pump1;3=hc2mixeropen;4=hc2mixerclose;5=hc2pump;6=col1pump;7=col2pump;8=valve2;9=valve3;10=legiopump;11=valve4;12=c1c2,,
w,,install,Ioteststop,stop I/O test,,,b506,01,
r,,,Currenterror,Current errors,,,b503,0001,error,,UIN,,,error number,error_1,,UIN,,,error number,error_2,,UIN,,,error number,error_3,,UIN,,,error number,error_4,,UIN,,,error number
r,,,Errorhistory,Error_History,,,b503,0101,index,m,UCH,,,,status,,UCH,,,Status,time,,VTM,,,time,date,,HDA:3,,,date,error,,UIN,,,error number
w,,install,Clearerrorhistory,Clear error history,,,b503,0201,cleared,s,UCH,0=no;1=yes,,