Notifications
You must be signed in to change notification settings - Fork 0
/
Copy path53.mc2.mc.5.csv
We can make this file beautiful and searchable if this error is corrected: It looks like row 2 should actually have 15 columns, instead of 2 in line 1.
116 lines (116 loc) · 15.3 KB
/
53.mc2.mc.5.csv
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
type,circuit,level,name,comment,qq,zz,pbsb,id,*name,part,type,divisor/values,unit,comment
*r,
*w,
r,,,StatPowerOn,StatPowerOn,,,b509,0dcc00,value,,UIN,,,
r,,,StatOperatingHours,StatOperatingHours,,,b509,0dcd00,value,,UIN,,,
r,,,StatMonthOfInstallation,StatMonthOfInstallation,,,b509,0dce00,value,,UCH,,,
r,,,StatYearOfInstallation,StatYearOfInstallation,,,b509,0dcf00,value,,UCH,,,
r,,,Stat15MinBusTimeout,Stat15MinBusTimeout,,,b509,0dd000,value,,UCH,,,
r,,,StatRTOSErrorcode,StatRTOSErrorcode,,,b509,0dd100,value,,UIN,,,
r,,,StatRestarts,StatRestarts,,,b509,0dd200,value,,UIN,,,
r,,,StatRTOSErrorCounter,StatRTOSErrorCounter,,,b509,0dd300,value,,UIN,,,
r,,,FlowTempDesired,DesiredFlowTemperature3: Desired flow temperature of MK2,,,b509,0d4600,value,,D1C,,°C,temperature
r,,,FlowTemp,Flow2Sensor3: Flow temperature,,,b509,0d0300,temp,,D2C,,°C,temperature,sensor,,UCH,0=ok;85=circuit;170=cutoff,,sensor status
r,,,OutsideTemp,OutsideTempSensor: current outside temperature (valid only if a sensor is connected to the VR60),,,b509,0d0600,temp,,D2C,,°C,temperature,sensor,,UCH,0=ok;85=circuit;170=cutoff,,sensor status
r,,,TeleSwitch,State of the Teleswitch,,,b509,0d0a00,value,,UCH,0=off;1=on,,
r,,,IsInHoliday,Holiday function active: Every bit of this byte represents a heating circuit; holiday function can be started by setting the HC's corresponding bit,,,b509,0d2700,value,,UCH,,,
r,,,IsInParty,IsInParty: Every bit of this byte represents a heating circuit; if bit is set the party function is activated for the corresponding HC,,,b509,0d4e00,value,,UCH,,,
r,,,CleaningLady,CleaningLady: saving function is activated until read value * 1/2 h,,,b509,0d4b00,value,,UCH,,,
r,,,IsInStorageFilling,IsInTankFilling: heating circuit is locked because of ongoing tank loading unless parallel loading has been activated,,,b509,0d4700,value,,UCH,0=no;1=yes,,
r,,,MixerDutyCycle,"Mixer2DutyCycle3: Telswitch,Pump,Circulation pump,DHW rewquest,DHW permittion",,,b509,0d0f00,value,,SCH,,,
r,,,HcPumpPort,Hk3P_Port3: Status of mixer cicuit pump on MK1P,,,b509,0d9400,value,,UCH,0=off;1=on,,
r,,,CfgHeatSinkType,CfgHeatSinkType3,,,b509,0d3c00,value,,UCH,0=disabled;1=mixer;2=water;3=fixvalue;4=backflow,,Type of the configurable mixer circuit
w,,install,CfgHeatSinkType,CfgHeatSinkType3,,,b509,0e3c00,value,,UCH,0=disabled;1=mixer;2=water;3=fixvalue;4=backflow,,Type of the configurable mixer circuit
r,,,OperatingMode,OperatingMode3: Operating mode of mixer circuit,,,b509,0d2b00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
w,,,OperatingMode,OperatingMode3: Operating mode of mixer circuit,,,b509,0e2b00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
r,,,TempDesired,DesiredTemperature3: Day temperature setpoint of the circuit,,,b509,0d3200,value,,D1C,,°C,temperature
w,,,TempDesired,DesiredTemperature3: Day temperature setpoint of the circuit,,,b509,0e3200,value,,D1C,,°C,temperature
r,,,TempDesiredLow,DesiredLowTemperature3: Night temperature setpoint of the circuit,,,b509,0d3300,value,,D1C,,°C,temperature
w,,,TempDesiredLow,DesiredLowTemperature3: Night temperature setpoint of the circuit,,,b509,0e3300,value,,D1C,,°C,temperature
r,,,HeatingCurve,HeatingCurve3: Heating curve,,,b509,0d3500,value,,UIN,100,,Heating curve
w,,,HeatingCurve,HeatingCurve3: Heating curve,,,b509,0e3500,value,,UIN,100,,Heating curve
r,,,OtShutdownLimit,"OtShutdownLimit3: For outside temperatures higher than this, there is no heat demand generated anymore",,,b509,0d3600,value,,UCH,,°C,desired temperature
w,,,OtShutdownLimit,"OtShutdownLimit3: For outside temperatures higher than this, there is no heat demand generated anymore",,,b509,0e3600,value,,UCH,,°C,desired temperature
r,,,HcPumpIdlePeriod,HcPumpIdlePeriod3: Time pump is not running in a pause at least,,,b509,0d4f00,value,,UCH,,min,minutes
w,,,HcPumpIdlePeriod,HcPumpIdlePeriod3: Time pump is not running in a pause at least,,,b509,0e4f00,value,,UCH,,min,minutes
r,,,FlowTempMin,MinFlowTemp3: For a heat demand the desired flow temperature will at least be this value,,,b509,0d3000,value,,UCH,,°C,temperature
w,,,FlowTempMin,MinFlowTemp3: For a heat demand the desired flow temperature will at least be this value,,,b509,0e3000,value,,UCH,,°C,temperature
r,,,FlowTempMax,MaxFlowTemp3: For a heat demand the desired flow temperature will maximal be this value,,,b509,0d3100,value,,UCH,,°C,temperature
w,,,FlowTempMax,MaxFlowTemp3: For a heat demand the desired flow temperature will maximal be this value,,,b509,0e3100,value,,UCH,,°C,temperature
r,,,HcMaxPreHeating,HcMaxPreHeating3: The heating start before a time window could shifted forwards maximal this time (related to the outside temperature),,,b509,0d3800,value,,UCH,,h,hours
w,,,HcMaxPreHeating,HcMaxPreHeating3: The heating start before a time window could shifted forwards maximal this time (related to the outside temperature),,,b509,0e3800,value,,UCH,,h,hours
r,,,TeleswitchOperatingMode,TeleswitchOperatingMode3: If the tele switch port is activated the mixer circuit operates in this mode,,,b509,0d3f00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
w,,,TeleswitchOperatingMode,TeleswitchOperatingMode3: If the tele switch port is activated the mixer circuit operates in this mode,,,b509,0e3f00,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
r,,,FloorPavingDryingDay,FloorPavingDryingDay3: Current day of floor paving drying routine,,,b509,0d3b00,value,,UCH,,,
w,,install,FloorPavingDryingDay,FloorPavingDryingDay3: Current day of floor paving drying routine,,,b509,0e3b00,value,,UCH,,,
r,,,CoolingRequest,CoolingRequest,,,b509,0db600,value,,UCH,0=no;1=yes,,
r,,,CoolingSupported,CoolingSupported,,,b509,0db900,value,,UCH,0=no;1=yes,,
r,,,DWMOffToHeatingDelay,DWMOffToHeatingDelay,,,b509,0db700,value,,UCH,,,
r,,,DWMOffToCoolingDelay,DWMOffToCoolingDelay,,,b509,0db800,value,,UCH,,,
r,,,CoolingStartOffset,CoolingStartOffset,,,b509,0dba00,value,,D1C,,,
w,,,CoolingStartOffset,CoolingStartOffset,,,b509,0eba00,value,,D1C,,,
r,,,CoolingModeStateCounter,CoolingModeStateCounter,,,b509,0dc000,value,,UCH,,,
r,,,CoolingEfficiencyState,CoolingEfficiencyState,,,b509,0dbd00,value,,UCH,,,
r,,,EfficiencyHysteresisMin,MinEfficiencyHysteresis,,,b509,0dbe00,value,,D1C,,,
r,,,TempDiffInOutdoor,TemperaturDiffInOutdoor,,,b509,0dc100,value,,D1C,,,
r,,,HcManualWorkingModeTriggeringActive,HCManualWorkingModeTriggeringActive,,,b509,0dc200,value,,UCH,,,
r,,,HcMode,HeatCircuitMode,,,b509,0dc300,value,,UCH,,,
r,,,HcModeAutomaticState,HeatCircuitModeAutomaticState,,,b509,0dc400,value,,UCH,,,
r,,,HcModeManualState,HeatCircuitModeManualState,,,b509,0dc500,value,,UCH,,,
r,,,CoolingOpmodeAutoState,CoolingOpmodeAutoState,,,b509,0dc600,value,,UCH,,,
r,,,CoolingModeAutomaticState,CoolingModeAutomaticState,,,b509,0dc700,value,,UCH,,,
r,,,CoolingWhileHolidaySupported,CoolingWhileHolidaySupported,,,b509,0dc800,value,,UCH,,,
r,,,RcRoomTemp,RcRoomTemp,,,b509,0dc900,value,,D2C,,°C,temperature
r,,,CoolingTimer_Monday,Periods Monday,,,b515,0003,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Monday,Periods Monday,,,b515,0003,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Tuesday,Periods Tuesday,,,b515,0103,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Tuesday,Periods Tuesday,,,b515,0103,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Wednesday,Periods Wednesday,,,b515,0203,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Wednesday,Periods Wednesday,,,b515,0203,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Thursday,Periods Thursday,,,b515,0303,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Thursday,Periods Thursday,,,b515,0303,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Friday,Periods Friday,,,b515,0403,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Friday,Periods Friday,,,b515,0403,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Saturday,Periods Saturday,,,b515,0503,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Saturday,Periods Saturday,,,b515,0503,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,CoolingTimer_Sunday,Periods Sunday,,,b515,0603,value,,IGN:1,,,,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,CoolingTimer_Sunday,Periods Sunday,,,b515,0603,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,DateTime,date/time,,,b504,00,dcfstate,,UCH,0=nosignal;1=ok;2=sync;3=valid,,DCF receiver state,btime,,BTI,,,time,bdate,,BDA,,,date,temp,,D2B,,°C,temperature
r,,,Mode,Operation mode,,,b504,01,tempdesired,,UCH,,°C,temperature,mcmode,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode,floorpavingdryingday,,UCH,,,days,floorpavingdryingtemp,,UCH,,°C,temperature,teleswitchmode,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode,mctype,,BI0:7,0=inactive;1=mixer;2=fixed;3=hwc;4=returnincr;5=pool;6=circulation,,mixer type,ign,,IGN,,,,daynight,,UCH,0=night;1=day;7=floorpaving,,day/night mode
w,,,SetTempDesired,Set desired temperature,,,b505,01,value,,UCH,,°C,temperature
w,,,SetMode,Set operation mode,,,b505,02,value,,UCH,0=disabled;1=on;2=off;3=auto;4=eco;5=low,,mixer mode
w,,,SetFloorPavingDryingDay,Set floor paving drying day,,,b505,03,value,,UCH,,,days
w,,,SetFloorPavingDryingTemp,Set floor paving drying temperature,,,b505,04,value,,UCH,,°C,temperature
w,,,SetType,Set type,,,b505,08,value,,UCH,0=inactive;1=mixer;2=fixed;3=hwc;4=returnincr;5=pool,,mixer type
w,,,SetTempDesiredLow,Set desired low temperature,,,b505,0a,value,,UCH,,°C,temperature
w,,,SetHeatingCurve,Set heating curve,,,b505,0b,value,,UIN,100,,Heating curve
w,,,SetShutdownTemp,Set outside shutdown temperature,,,b505,0c,value,,UCH,,°C,temperature
w,,,SetPumpIdlePeriod,Set pump idle period,,,b505,0d,value,,UCH,,min,minutes
w,,,SetFlowTempMin,Set min flow temperature,,,b505,0e,value,,UCH,,°C,temperature
w,,,SetFlowTempMax,Set max flow temperature,,,b505,0f,value,,UCH,,°C,temperature
w,,,SetMaxPreHeating,Set max pre-heating,,,b505,10,value,,UCH,-12,h,hours
r,,,Params,Parameters,,,b504,09,tempdesired,,UCH,,°C,temperature,tempdesiredlow,,SCH,,°C,temperature,curve,,UIN,100,,Heating curve,mctype,,BI0:7,0=inactive;1=mixer;2=fixed;3=hwc;4=returnincr;5=pool;6=circulation,,mixer type,shutdowntemp,,SCH,,°C,temperature,pumpidleperiod,,UCH,,min,minutes,flowtempmin,,SCH,,°C,temperature,flowtempmax,,SCH,,°C,temperature,maxpreheating,,UCH,-12,h,hours
r,,,Status0a,Status flow temperature/mixer/pump/desired flow temperature,,,b504,0a,flowtemp,,D2C,,°C,temperature,mixer,,UCH,0=off;1=open;2=close,,mixer State,pump,,UCH,0=off;1=on,,,onoff,,UCH,0=off;1=on,,,flowtempdesired,,UCH,,°C,temperature
r,,,Status,Status flow desired/current,,,b504,0d,flowtempdesired,,UCH,,°C,temperature,onoff,,UCH,0=off;1=on,,,flowtemp,,D2C,,°C,temperature,tempdesired,,UCH,,°C,temperature
r,,,Status16,outside temperature,,,b504,16,value,,D2C,,°C,temperature
r,,,Timer_Monday,Periods Monday,,,b504,02,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Monday,Periods Monday,,,b505,0901,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Tuesday,Periods Tuesday,,,b504,03,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Tuesday,Periods Tuesday,,,b505,0902,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Wednesday,Periods Wednesday,,,b504,04,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Wednesday,Periods Wednesday,,,b505,0903,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Thursday,Periods Thursday,,,b504,05,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Thursday,Periods Thursday,,,b505,0904,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Friday,Periods Friday,,,b504,06,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Friday,Periods Friday,,,b505,0905,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Saturday,Periods Saturday,,,b504,07,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Saturday,Periods Saturday,,,b505,0906,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Timer_Sunday,Periods Sunday,,,b504,08,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
w,,,Timer_Sunday,Periods Sunday,,,b505,0907,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,from,,TTM,,,from,to,,TTM,,,to,daysel,,UCH,0=selected;1=Mo_Fr;2=Sa_Su;3=Mo_Su,,days
r,,,Currenterror,Current errors,,,b503,0001,error,,UIN,,,error number,error_1,,UIN,,,error number,error_2,,UIN,,,error number,error_3,,UIN,,,error number,error_4,,UIN,,,error number
r,,,Errorhistory,Error_History,,,b503,0101,index,m,UCH,,,,status,,UCH,,,Status,time,,VTM,,,time,date,,HDA:3,,,date,error,,UIN,,,error number
w,,install,Clearerrorhistory,Clear error history,,,b503,0201,cleared,s,UCH,0=no;1=yes,,
w,,,RoomTempOffset,Room offset calculation,,,b505,2d,value,,D2C,,°C,temperature
w,,,Party,Quick - party,,,b505,05,value,,UCH,0=off;1=on,,
w,,,Load,quick - hot water tank filling,,,b505,06,value,,UCH,0=off;1=on,,
w,,,Save,Quick - cleaning lady,,,b505,07,value,,TTH,,,